Hyamat SVP
Main applications
- Building services
- Fire fighting and sprinkler systems
- Pressure boosting, fire fighting systems
- Water supply
Technical data
Q max
660.0 m³/h
H max
160.0 m
Design
Fully automatic package pressure booster system with 2 to 6 vertical high-pressure pumps and continuously variable speed adjustment of all pumps by PumpDrive; for fully electronic control of the required supply pressure. Design and function as per DIN 1988. Automated with BoosterControl and PumpDrive.
Application
Pressure boosting in residential buildings, hospitals, office buildings, hotels, department stores, industry, etc.
Further technical information about Hyamat SVP
Overview of technical data
Q (50Hz) | 0.0 – 660.0 (m³/h) |
H (50Hz) | 6.0 – 160.0 (m) |
Type of bearing | Plain bearings |
Drive frequency | 50 Hz |
Type of drive | Electric motor |
Drive voltage | Low voltage |
Type of first impeller | Closed / Radial |
Other impeller types | Closed / Radial |
Impeller material (EN standard) | 1.4301 |
Type of coupling | Direct |
Type of lubrication | Product lubrication |
Max. permissible fluid temperature | 70.0 (°C) |
Nozzle position | In-line |
Number of pumps | 6 |
Maximum operating pressure | PN 16 |
Pump set location | Dry installed |
Suction characteristics | Non-priming |
Suitable for drinking water | Yes |
Type of connection | Screw-ended, flange |
Type of stage casing | Stage casing with diffuser |
UNSPSC classification | 4015150300 |
Casing material (EN standard) | 1.4301 |
eClass assignment | 36410101 |
Maximum inlet pressure | 10.0 (bar) |
Installation position | Vertical |
Shaft seal type | Mechanical seal |
Main applications | Industry and process engineering, Water, Building services |
Casing material | Chrome nickel steel |
Maximum discharge-side pressure | 16.0 (bar) |
Maximum drive rating | 22.0 (kW) |
Type of installation | Stationary |
Maximum speed of rotation | 3000.0 (1/min) |
Standby pump | Yes |
Type of connection | Indirect and direct |