LevelControl Advanced 1
Aplicaciones principales
- Aguas residuales
- Drenaje
- Drenaje de superficies
- Edificaciones
- Estaciones de bombeo para drenaje
- Residuos
- Unid. de elevación de aguas residuales
- Unidades de elevación para residuos
Design
LevelControl BU:
Pump control module in DIN rail design with optional, separate display
for installation in control cabinet doors with external load circuit to
EN 60 439. LevelControl BU controls and protects up to two pumps and is
used in conjunction with further expansion work to the control cabinet.
For draining tanks via float switches, hydrostatic pressure, 4...20mA
sensor input.
LevelControl CU:
Compact low-voltage switchgear with graphic display for controlling and
monitoring one or two pumps. D.o.l. starting up to 4 kW. For draining
tanks via float switches, hydrostatic pressure, 4...20mA sensor input.
LevelControl SU:
Low-voltage switchgear with optional graphic display for controlling and
monitoring one or two pumps. D.o.l. starting up to 4 kW, star-delta
starting up to 22 kW. For draining tanks via float switches, hydrostatic
pressure, 4...20mA sensor input.
Más información técnica sobre LevelControl Advanced 1
Resumen de los datos técnicos
Bucle de control abierto / cerrado | Control de circuito abierto |
Método inicial | Directo, Estrella-triángulo |
Voltaje | 3~400V AC, 1~230V AC |