Hya-Solo D

Hya-Solo D


Main applications

  • Building services
  • Fire fighting and sprinkler systems
  • Pressure boosting, fire fighting systems
  • Water supply

Design type

Pressure boosting units

Technical data

Q max 65.0 m³/h
H max 150.0 m

Design

Fully automatic package single-pump system with 8 l membrane-type accumulator, pressure-controlled starting and stopping.

Applications

For industrial plants, water supply systems for residential and office buildings, irrigation/spray irrigation and rainwater harvesting systems, service water supply systems in trade and industry.

Further technical information about Hya-Solo D

Overview of technical data

Q (50Hz) 0.0 – 65.0 (m³/h)
H (50Hz) 10.0 – 150.0 (m)
Type of bearing Plain bearings
Drive frequency 50 Hz
Type of drive Electric motor
Drive voltage Low voltage
Type of first impeller Closed / Radial
Other impeller types Closed / Radial
Impeller material (EN standard) 1.4301
Type of installation Long-coupled
Type of coupling Direct
Type of lubrication Product lubrication
Discharge casing material (EN standard) 1.4301
Max. permissible fluid temperature 70 (°C)
Nozzle position In-line
Number of pumps 1
Maximum operating pressure 16 BAR
Pump set location Dry installed
Stage casing material (EN standard) 1.4308
Suction characteristics Non-priming
Suitable for drinking water Yes
Type of connection Screw-ended, flange
Type of stage casing Stage casing with diffuser
Type of suction casing 00
UNSPSC classification 4015150300
Casing material (EN standard) 1.4301
eClass assignment 00000000, 36410101
Maximum inlet pressure 6 (bar)
Minimum inlet pressure 0,50 (bar)
Installation position Vertical
Shaft seal type Mechanical seal
Main applications Industry and process engineering, Water, Building services
Casing material Chrome nickel steel
Maximum discharge-side pressure 16 (bar)
Maximum drive rating 22 (kW)
Type of installation Stationary
Maximum speed of rotation 2900 (1/min)
Type of connection Direct