ES000323-BOA-Control-BOA-Control-IMS

BOA-Control/BOA-Control IMS


Principais utilizações

  • Aquecimento, ventilação, ar condicionado
  • Calefação , ar condicionado
  • Edifícios
  • Tratamento de superfície

Dados técnicos

T max 120 °C
DN max 350
PN max 16

Design

Balancing valve with electronic sensor for flow and fluid temperature measurement with BOATRONIC M-2 measuring computer for hydraulic balancing with short-term measurement, with BOATRONIC M-420 for analog signal transfer, e.g. to a control room. Independent of minimum differential pressures; constant accuracy across the entire range of valve travel. Standard: locking device and travel stop. Maintenance-free, full insulation possible.

Application

Hot water heating systems up to 120 °C. Cold water for air-conditioning systems. Not suitable for fluids containing mineral oils, steam or fluids liable to attack EPDM and uncoated cast iron, for example in open cooling circuits.

Mais informações técnicas sobre BOA-Control/BOA-Control IMS

Vista geral dos dados técnicos

T -10 – 120 (°C)
DN 15 – 350
PN 16
Opções de comandos disponíveis ex works Acionamento elétrico semelhante ao BOA-CVE SuperCompact
Design do corpo Corpo de passagem reto
Dimensões padrões EN558/1 ISO5752/1
Medição da vazão em volume sim, medição de ultra-sons com detecção de temperatura
Movimento do volante manual Não crescente
Vedação na passagem Vedação Metalica e macia
Execução da conexão tubular Execução do flange
Vedação da haste Anel de vedação
Material do corpo (EN padrão) JL 1040
Região de aplicação principal Housing (Residencial)
Material do corpo Ferro Fundido
Elemento de vedação do Corpo/Castelo Nenhum (corpo de peça única)